Instruction book
The interpretation of the values obtained is :
RSI < 6 boiler scale formation
RSI 6 - 7 neutral water
RSI > 7 corrosive water
A more detailed interpretation follows below :
RSI Tendency of the water Action
RSI < 3.9 Very high scale formation Water cannot be used
4.0 < RSI < 5.5 High boiler scale formation Regular control and descaling operation necessary
5.6 < RSI < 6.2 Slight boiler scale formation Water treatment not necessary
6.3 < RSI < 6.8 Neutral water Occasional inspection recommended
6.9 < RSI < 7.5 Slight corrosion at higher temperature
7.6 < RSI < 9.0 Strong corrosion Regular control necessary, use of corrosion inhibitor
recommended
9.1 < RSI < 11 Very strong corrosion Regular control necessary, use of corrosion inhibitor
required
RSI > 11 Very strong corrosion in complete water system Water should not be used
This table indicates that distilled or demineralised water should
never be used, as their RSI is >11.
The RSI is only indicating the equilibrium of scaling descaling.
A cooling water showing good RSI conditions can still be
unsuitable due to other factors.
From the table above, the RSI index should be between 5.6
and 7.5, otherwise contact specialist.
pH
The effect of pH is already incalculated in the Rysnar index,
but the pH itself has some additional limitations :
GA/GR-units 6.8 < pH
Total Dissolved solids (TDS)
This is the sum of all ions in the water. It can be derived from
the dry residue after evaporation (but not including suspended
solids), or it can be estimated from the electrical conductivity.
In a closed system, the following limits apply :
All units TDS < 3000 mg/l (<3800 µS/cm)
For an open system, the following limits apply :
GA/GR-units TDS < 450 mg/l ( < 580 µS/cm)
Chlorides (Cl
-
)
Chloride ions will create pitting corrosion on stainless steel.
Their concentration should be limited :
Closed cooling system : Chlorides < 500 ppm
Open cooling system : Chlorides < 150 ppm
However, if the water is scaling, lower limits should be used.
(See The Rysnar stability index (RSI)).