- 107 -
Power circuit Circuit-breaker, 3ph.
Number of poles 4 4
Thermal release It (thermal release is higher at 25°C) 100 A 100 A
Magnetic release Im 3..5xIn 3..5xIn
Circuit-breaker, 3ph., lower voltage
Number of poles (optional) 3 4
Thermal release It (thermal release is higher at 25°C) 152 A 175 A
Magnetic release Im 3..5xIn 3..5xIn
Circuit-breaker, 1ph.
Number of poles (optional) 3 4
Thermal release It (thermal release is higher at 25°C) 175 A 187.5 A
Magnetic release Im 3..5xIn 3..5xIn
Fault current protection
Residual current release IDn 0.030-30 A 0.030-30 A
Insulation resistance (optional) 10-100 kOhm 10-100 kOhm
Outlet sockets (optional) i) domestic
Following three socket configuration is possible: 2p + PE
1. i + ii + iii + iv 16 A/230 V
2. i + ii + iii + iv (2x)
3. i + ii + iii + iv + v ii) CEE form
3p + N + PE
16 A/400 V
iii) CEE form
3p + N + PE
32 A/400 V
iv) CEE form
3p + N + PE
63 A/400 V