TOPPING UP AFTER LIMITED QUANTITY DRAINING FROM THE COOLING SYSTEM
The quantity of PARCOOL EG Concentrate to be topped up after draining a calculated volume from the cooling system, can be estimated with the following formula and/or graph:
Corrections concentrate in measured system towards 50% volume by using PARCOOL EG Concentrate
80
33
33
33
17
67
80 67 20
50-
100-
==*/
=
Example:
Total volume coolant =
Measured concentration =
Liter
Vol %
PN: 1604 8159 00
4 8 12 16 20 24 28 32 36 40 44 48 52 56 60 64 68 72 76 80 84
0,0
2,5
5,0
7,5
10,0
12,5
15,0
17,5
20,0
22,5
25,0
1
2
3
4
5
Engine coolant capacity (liter)
Top-up volume PARCOOL EG Concentrate with drainage
Liter PARCOOL EG Concentrate
In case of expansion tank at low level, this quantity is to be
filled without draining from the cooling system.
1. Refractometer indication -20° C (33%)
2. Refractometer indication -22° C
3. Refractometer indication -25° C
4. Refractometer indication -30° C
5. Refractometer indication -36° C
Top-up volume (liter)