EasyManuals Logo

AUMA AUMATIC ACExC 01.2 User Manual

AUMA AUMATIC ACExC 01.2
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
DescriptionValueDesignation
(process representation)
Bit
No command (reserved)5
No command (reserved)6
No command (reserved)7
Bits 0, 1, 2 = operation
commands
Bits 0 2 are used to transmit operation commands to the actuator. Only one of
these bits may be set to 1 at any given time. If several bits are set, no operation is
performed and the following signal is given: Wrong oper. cmd
For operation commands via bit 2 (Fieldbus SETPOINT):
Condition: Position transmitter (potentiometer, RWG, EWG or MWG) installed
in the actuator
If the setpoint is 0 per mil, the actuators runs to the end position CLOSED; it
runs to the end position OPEN for 1000 per mil.
If the limit of 1,000 is exceeded, the actuator completely runs to end position
OPEN.
To avoid placing too much strain on the mechanics, the reversing of direction
is delayed.The default setting in the factory for the reversing prevention time
is 300 ms.
Bits 4, 5, 6 , 7
Bits 4 through 7 are not used and must be set to 0.
Byte 2: Reserved 1
The contents are reserved for future extensions.
Bytes 3 and 4: Setpoint position /(process setpoint, option)
Byte 3 = high byte, byte 4 = low byte.
The setpoint position is transmitted via bytes 3 and 4 (value: 0 1,000), using the
position controller.
The value 1,000 corresponds to the maximum setpoint, i.e. end position OPEN.
The value 0 corresponds to the minimum setpoint, i.e. end position CLOSED.
As an alternative, the process setpoint can be transmitted via bytes 3 and 4 (value
0... 1,000), using a process controller (option). Value 1,000 corresponds to the
maximum process setpoint, value 0 to the minimum process setpoint.
Byte 5: Additional commands
Table 28: Byte 5: Additional commands
DescriptionValueDesignation
(process representation)
Bit
Actuator operation via local controls enabled1
Fieldb. enable LOCAL
0
Actuator operation via local controls disabled0
Enabling operation command in direction OPEN1
Fieldb. enable OPEN
1
Operation command in direction OPEN disabled.0
Enabling operation command in direction CLOSE1
Fieldb. enable CLOSE
2
Operation command in direction CLOSE disabled.0
No command (reserved)3
Initiate change-over to channel 11
Fieldbus channel 1
4
No operation command0
Initiate change-over to channel 21
Fieldbus channel 2
5
No operation command0
EMERGENCY signal, triggers EMERGENCY beha-
viour.
1
Fieldbus EMCY
6
No command0
Start Partial Valve Stroke Test (functional test)1
PVST
7
No operation command0
36
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA AUMATIC ACExC 01.2 and is the answer not in the manual?

AUMA AUMATIC ACExC 01.2 Specifications

General IconGeneral
BrandAUMA
ModelAUMATIC ACExC 01.2
CategoryController
LanguageEnglish

Related product manuals