9. Signals (output signals)
The precise version is indicated in the terminal plan or on the order-related technical
data sheet.
9.1. Digital outputs
Table 9:
Designation in the wiring diagramMessage
Limit switch, closing, clockwise rotation = end position switch CLOSEDWEREnd position OPEN/CLOSED
reached
Limit switch, closing, counterclockwise rotation = end position switch OPENWEL
WER/WEL are used to switch off the motor for limit seating in the end positions (end position switches).
These switches are used for motor current transport. Consequently, they are not appropriate for sig-
nalling.
Setting via limit switches page 19, Limit switching: set
Additional limit switches in direction OPENWE 1Option
End position OPEN/CLOSED
reached
Intermediate position reached
Additional limit switches in direction CLOSEWE 2
WE 1/WE 2 are additional limit switches for signalling the end positions OPEN/CLOSED or intermediate
positions.
Setting via limit switches page 19, Limit switching: set
Torque switch, closing, clockwise rotation (CLOSE)DERTorque OPEN/CLOSED reached
Torque switch, opening, counterclockwise rotation (OPEN)DEL
DER/DEL switch off the motor if the factory torque setting has been reached.These switches are used
for motor current transport. Consequently, they are not appropriate for signalling.
Additional torque switch, closing, clockwise rotation (CLOSE)DE1Option
Torque OPEN/CLOSED reached
Additional torque switch, opening, counterclockwise rotation (OPEN)DE2
DE 1/DE 2 are additional potential-free switches for torque signalling OPEN/CLOSE.
Factory setting (cannot be changed).
ThermoswitchesOption
Motor protection tripped
ThermoswitchesHz
9.2. Analogue outputs
Table 10:
Depending on the version, via potentiometer or electronic position transmitter ESR100 or positioner
(positioning electronics) PEL 100
Option
Position feedback signal
PotentiometerR1
Potentiometer in tandem arrangement (option)R2
Electronic position feedback signal 2-wire system (4 20 mA)ESR
Electronic position feedback signal 3- 4-wire system (0/4 20 mA)ESR