effectively by inserting the double sealed intermediate frame [2] between the
plug/socket connector [1] and the housing of the device.The enclosure protection
of the device (IP68) will not be affected, even if the electrical connection [1] is
removed.
6.4.4. External earth connection
Figure 35: Earth connection for multi-turn actuator
Application
External earth connection (U-bracket) for connection to equipotential compensation.
Table 22:
Terminal cross sections and earth connection tightening torques
Tightening torquesTerminal cross sectionsConductor type
3 4 Nm2.5 mm² to 6 mm²Solid wire and stranded
3 4 Nm1.5 mm² to 4 mm²Fine stranded
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.