EasyManua.ls Logo

AUMA SA 07.2 - 8.3. Indication lights of local controls

AUMA SA 07.2
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.3. Indication lights of local controls
Figure 65: Arrangement and signification of indication lights
[1] Marking with symbols (standard)
[2] Marking with figures 1 6 (option)
1
End position CLOSED reached (blinking: operation in direction CLOSE)
2 Tc Torque fault CLOSE
3
Motor protection tripped
4 To Torque fault OPEN
5
End position OPEN reached (blinking: operation in direction OPEN)
6
Bluetooth connection active
Modify indication light assignment (indications)
Different indications can be assigned to LEDs 1 5.
Device configuration M0053
Local controls M0159
Indication light 1 (left) M0093
Indication light 2 M0094
Indication light 3 M0095
Indication light 4 M0096
Indicat. light 5 (right) M0097
Signal interm. pos. M0167
Defaut values (Europe):
Indication light 1 (left) = End p. CLOSED, blink
Indication light 2 = Torque fault CLOSE
Indication light 3 = Thermal fault
Indication light 4 = Torque fault OPEN
Indicat. light 5 (right) = End p. OPEN, blink
Signal interm. pos. = OPEN/CLOSED = Off
Further setting values:
Refer to Manual (Operation and setting).
52
SA 07.2 SA 16.2 / SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
Indications AC 01.2 Non-Intrusive DeviceNet

Table of Contents

Other manuals for AUMA SA 07.2

Related product manuals