Service conditions
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Available colours on requestOption:
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN ISO 22153. Detailed inform-
ation can be provided on request.
Lifetime
< 72 dB (A)Noise level
Further information
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
EU Directives
Dimensions SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
Dimensions SA 07.2 – SA 14.6/SAR 07.2 – SAR 14.6
Electrical data SA 07.2 – SA 16.2
Electrical data SAR 07.2 – SAR 16.2
Electrical data SA 07.2 – SA 14.6
Electrical data SAR 07.2 – SAR 14.6
Reference documents
14.2. Technical data Actuator controls
Features and functions
Refer to name plate
Permissible variation of mains voltage: ±10 %
Permissible variation of mains voltage: ±30 % (option)
Permissible variation of mains frequency: ±5 %
Power supply
24 V DC: +20 %/-15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
External supply of the electronics
(option)
Current consumption of the actuator controls depending on mains voltage:
For permissible variation of mains voltage of ±10 %:
●
100 to 120 V AC = max. 740 mA
●
208 to 240 V AC = max. 400 mA
●
380 to 500 V AC = max. 250 mA
●
515 V AC = max. 200 mA
For permissible variation of mains voltage of ±30 %:
●
100 to 120 V AC = max. 1,200 mA
●
208 to 240 V AC = max. 750 mA
●
380 to 500 V AC = max. 400 mA
●
515 to 690 V AC= max. 400 mA
Current consumption
Category III according to IEC 60364-4-443Overvoltage category
The actuator controls are designed for the nominal motor power, refer to motor name plateRated power
Reversing contactors (mechanically and electrically interlocked) for AUMA power classes
A1/A2
Standard:Switchgear
Reversing contactors (mechanically and electrically interlocked) for AUMA power class
A3
Options:
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power classes B1, B2 and B3
The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high
number of starts, we recommend the use of thyristor units.
For the assignment of AUMA power classes, please refer to Electrical data on actuator
Via DeviceNet interfaceControl and feedback signals
92
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit: electronic (MWG)
Technical data AC 01.2 Non-Intrusive DeviceNet