Figure 70: Gateway range“Application”
For this, parameter 5277 Connection type M1976 must be additionally configures in
the actuator controls:
Connection type = 1 (AM Triple Play)
or
Connection type = 5 (DeviceNet like AC 01.1)
Possible settings are:
AM Triple Play
Input data (Produced Data):
CDN455: Standard Input Data – rotary coding switch S4 = 0
CDN215: Standard Input Data – rotary coding switch S4 = 9
Output data (Consumed Data):
Standard Output Data – rotary coding switch S5 = 0
DeviceNet like AC 01.1
Input data (Produced Data):
Standard Input – rotary coding switch S4 = 1
Extended Input – rotary coding switch S4 = 2
Extended One Analog Input – rotary coding switch S4 = 3
Extended Two Analog Input – rotary coding switch S4 = 4
Enhanced Input – rotary coding switch S4 = 5
Process Input Data 1 – rotary coding switch S4 = 6
Process Input Data 2 – rotary coding switch S4 = 7
Process Input Data 3 – rotary coding switch S4 = 8
Output data (Consumed Data):
Standard Output – rotary coding switch S5 = 1
Standard One Analog Output – rotary coding switch S5 = 2
Process Output – rotary coding switch S5 = 3
62
SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.2 Non-Intrusive DeviceNet