16. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT C:ESC
AENDERN M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
17. Return to status display:
Press C several times until S0 is displayed.
9.3 Baud rate, parity and bus addres (slave addess): set
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
MODBUS 1 (M1F)
BAUDRATE (M1F11)
PARITY (M1F12)
SLAVEADDRESS (M1F14)
Setting ranges and default values:
BAUDRATE: 300 38 400 BAUD (4 800 BAUD)
PARITAET: (EVEN, 1 STOPBIT)
ODD, 1 STOPBIT
NO, 2 STOPBITS
SLAVEADRESSE: 1 247 (247)
Step by step:
1. Set selector switch to position 0 (OFF).
2.
Press C and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
42
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electromechanic
Commissioning (basic settings) AC 01.1 Intrusive Modbus RTU