AUMA SA 10.1 - Modbus Interface

AUMA SA 10.1
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The reversing contactors are designed for a lifetime of 2 million starts.1)
For the assignment of AUMA power classes, please refer to electrical data on actuator.2)
Not possible in combination with PTC tripping device3)
During an adjustable period (factory setting 10 seconds), faults in the supply voltage (e.g. voltage drops) will not lead to a fault signal.4)
Requires position transmitter in actuator5)
Requires position transmitter in actuator6)
Requires position transmitter in actuator7)
Further options for version with potentiometer or RWG in the actuator
Start and end of stepping mode as well as ON and OFF time (1 up to 300 seconds) can be
programmed individually for the directions OPEN and CLOSE.
Timer
Any 8 intermediate positions between 0 and 100 %, reaction and signal behaviour program-
mable
Intermediate positions
12.3 Modbus interface
Settings/programming the Modbus interface
Baud rate, parity and Modbus address are set via the display of the AUMATIC.Setting the Modbus interface
Commands and signals of the fieldbus interface
OPEN, STOP, CLOSE, position setpoint
1)
, RESETProcess representation output
(command signals)
End position OPEN, CLOSED
Actual position value
2)
Actual torque value
3)
Selector switch in position LOCAL/REMOTE
Running indication
4)
(directional)
Torque switch OPEN, CLOSE
Limit switch OPEN, CLOSED
Manual operation by handwheel
5)
or via local controls
2 analogue and 4 digital customer inputs
Process representation input
(feedback signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Loss of the analogue customer inputs
Process representation input
(fault signals)
The behaviour of the actuator is programmable:
Stops in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
6)
Behaviour on loss of communi-
cation
Requires position transmitter in actuator1)
Requires position transmitter in actuator2)
Requires magnetic limit and torque transmitter (MWG) in actuator3)
Requires position transmitter in actuator4)
Requires position transmitter in actuator5)
Requires position transmitter in actuator6)
General fieldbus interface data
Modbus RTUCommunication protocol
Line (bus) structure
Active bus termination at both ends
Coupling and uncoupling of devices during operation without affecting other devices is
possible
Network topology
Twisted, screened copper cable according to IEC 61158Transmission medium
EIA-485 (RS485)Fieldbus interface
66
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electromechanic
Technical data AC 01.1 Intrusive Modbus RTU