EasyManua.ls Logo

AUMA SAM Ex 07.1 - Function of the Diagnosis Leds (Timer); 17 Timer (Option)

AUMA SAM Ex 07.1
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Example:
Two actuators are to be operated in Split Range version. Actuator 1 must be
in position CLOSED with a nominal value signal E1 of 0 mA, and in position
OPEN with a signal of 10 mA.
Actuator 2 must be in position CLOSED with a nominal value signal of
10 mA, and in position OPEN with a signal of 20 mA.
.
Positioner actuator 1:
Supply E1 = 0 mA, set with P5 = 0 V at M3,
supply E1 = 10 mA, set with P6 = 5V at M9.
.
Positioner actuator 2:
Supply E1 = 10 mA, set with P5 = 2,5 V at M3,
supply E1 = 20 mA, set with P6 = 5 V at M9.
.
Perform adjustments and settings for E2 etc. Afterwards the nominal value
E1 can be transmitted through both actuators (can be connected in
series). When operating within range E1 = 0 - 10 mA the actuator 1
moves, actuator 2 remains in end position CLOSED. When operating
within range E1 = 10 - 20 mA the actuator 2 moves, actuator 1 remains in
end position OPEN.
17. Timer (option) With the timer board the operating time can be increased for the entire or
any portion of the valve travel.
Example:
In order to avoid water hammer in long pipelines, stepping mode can be
chosen for each part of the travel.
.
The timer is installed in the AUMA MATIC Ex instead of the interface
board (figure P, page 19).
.
Electronic timer is not possible in combination with positioner.
17.1 Function of the diagnosis LEDs (timer)
V14 is illuminated: Phase failure and/or motor protection tripped,
Reset by selector switch to position III at local controls
V15 is illuminated: Torque fault: Torque switch operated in
mid-travel
V21 is illuminated: Stepping mode in direction CLOSE switched on
V22 is illuminated: Stepping mode in direction OPEN switched on
28
Multi-turn actuators SAM Ex 07.1 - SAM Ex 16.1 / SARM Ex 07.1 - SARM Ex 16.1
AUMA MATIC Ex Operation instructions
R11
R10 R12
R13
Figure U: Cover plate timer A1.6

Table of Contents