10.
Return to the VIEW/EDIT menu:
Press C twice.
Change settings:
11.
Press .
Display indicates:
MODBUS 1 M1F1
VIEW
EDIT
12.
Press .
Display indicates:
ENTER PASSWORD
0 * * *
:EDIT :OK C:ESC
13. Enter password:
Press 4 x = 0000 (default factory password).
Display indicates:
EDIT M1F11
BAUDRATE
PARITY
CONNECT-CONTROL TIME
14.
Use to select BAUDRATE, PARITY or SLAVEADDRESS and confirm se-
lection with .
Display shows the selected value. Example SLAVEADDRESS:
EDIT M1F14
SLAVEADDRESS
1
:EDIT C:ESC
15.
Press again to enter the edit mode.
Display indicates:
EDIT M1F14
SLAVEADDRESS
1
:EDIT :OK C:ESC
16. Set new value:
Press .
44
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electromechanic
Commissioning (basic settings) AC 01.1 Intrusive Modbus RTU