5.3. SJ electrical connection (AUMA plug/socket connector)
Figure 18: SJ electrical connection
[1] Terminal compartment (in cover)
[1A] Cable entries for mains connection (power and control contacts)
[1B] Cable entries for fieldbus cables
[2] Socket carrier with screw-type terminals
Short description
Plug-in electrical connection with screw-type terminals for power and control contacts.
Control contacts also available as crimp-type connection as an option.
SJ version . For power and control cable connection, remove the AUMA plug/socket
connector and the socket carrier from terminal compartment. Removing the cover
is sufficient for connecting the fieldbus cables.
Technical data
Table 19:
Electrical connection via AUMA plug/socket connector
Control contactsPower contacts
50 pins/sockets6 (3 equipped) + protective
earth conductor (PE)
No. of contacts max.
1 to 50U1, V1, W1, U2, V2, W2, PEDesignation
250 V750 VConnection voltage max.
16 A25 ARated current max.
Screw connection, crimp-type (option)Screw connectionType of customer connection
2.5 mm
2
(flexible or solid)
6 mm
2
(flexible)
10 mm
2
(solid)
Connection diameter max.
Information
For some special motors, the connection of the power terminals (U1, V1, W1, U2,
V2, W2) is not performed via the AUMA plug/socket connector but via a terminal
board directly at the motor.
26
SA 07.2 SA 16.2 / SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
Electrical connection AC 01.2 Non-Intrusive EtherNet/IP