EasyManua.ls Logo

AUMA SAR 07.6 - Page 84

AUMA SAR 07.6
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Features and functions
Terminal plan according to order number enclosed with deliveryTerminal plan
B1 according to EN ISO 5210Standard:Valve attachment
A, B2, B3, B4, C, D according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Option:
Special valve attachments: AF, AK, AG, B3D, ED, DD, IB1, IB3
A prepared for permanent lubrication of stem
Electronic control unit (option)
Magnetic limit and torque transmitter (MWG)
Turns per stroke: 1 to 500 (standard) or 10 to 5,000 (option)
Non-Intrusive setting
Via actuator controlsPosition feedback signal
Via actuator controlsTorque feedback signal
Continuous self-adjusting indication with symbols OPEN and CLOSEDMechanical position indicator
Blinking signal via actuator controlsRunning indication
Resistance type heater with 5 W, 24 V ACHeater in switch compartment
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level, on request
Installation altitude
Refer to actuator name plateAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP68 (with AUMA 3-phase/1-phase AC or DC motor)
For special motors differing enclosure protection available (refer to motor name plate)
Standard:Enclosure protection according to
EN 60529
DS Terminal compartment additionally sealed against interior (double sealed)Option:
According to AUMA definition, enclosure protection IP68 meets the following requirements:
Depth of water: Maximum 8 m head of water
Duration of continuous immersion in water: Maximum 96 hours
Up to 10 operations during flooding.
Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to IEC
60664-1
2 g, from 10 to 200 Hz (for actuators in AUMA NORM version)
1 g, from 10 to 200 Hz (for actuators with mounted AUMA actuator controls)
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Indications apply to actuators with AUMA 3-phase AC motor and AUMA plug/socket
connector.They are not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Option:
KX-G : same as KX, however aluminium-free version (outer parts)
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Other colours are possible on request.Option:
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. For further details,
please contact AUMA
Lifetime
< 72 dB (A)Noise level
84
SA 07.2 SA 16.2 / SAR 07.2 SAR 16.2 Control unit: electronic (MWG)
Technical data AC 01.2 Non-Intrusive EtherNet/IP

Table of Contents

Other manuals for AUMA SAR 07.6