2. Switch on actuator in direction CLOSE and observe the direction of rotation on
the mechanical position indication:
For self-adjusting mechanical position indication:
The direction of rotation is correct if the actuator operates in direction
CLOSE and arrow turns clockwise in direction CLOSE (symbol ).
Figure 63: Direction of rotation (for clockwise closing version)
For mechanical position indication via indicator mark: (not self-adjust-
ing)
The direction of rotation is correct if the actuator operation in direction
CLOSE and the symbols ( / ) turn counterclockwise:
Figure 64: Direction of rotation / (for clockwise closing version)
63
SAEx 07.2 SAEx 16.2 / SAREx 07.2 SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profinet Commissioning (basic settings)