EasyManua.ls Logo

AUMA SEVEN 2SA7 - Page 17

AUMA SEVEN 2SA7
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electric Rotary Actuators 2SA7
Technical Data
Y070.304/EN Page 17
Electrical data – Control and feedback signals
1 2 3 4 5 6 7 - 8 9 10 11 12 13 14 15 16
2SA7
- -
3
ECOTRON: 3 binary inputs 24/48 V DC (OPEN, CLOSE, STOP), 5 binary outputs 24/48 V DC
1 analog output 4 – 20 mA (actual position value), segment display (symbols for parameterization/commissioning)
4
PROFITRON: 5 binary inputs 24/48 V DC (OPEN, CLOSE, STOP, EMERGENCY, Mode), 8 binary outputs 24/48 V DC,
1 analog output 0/4 – 20 mA (actual position value), multicolor graphic display with status indication
A
electronics unit without hardware extension
B
relay board with 5 outputs for ECOTRON, 8 for PROFITRON
C
PROFIBUS DP 1 channel - with V1 and V2 services
D
PROFIBUS DP 2 channel - with V1 and V2 services
E
MODBUS RTU 1 channel
F
MODBUS RTU 2 channel
J
HART (only PROFITRON) ECOTRON PROFITRON
K
HART + relay board (only PROFITRON)
2SA7. 2SA70 2SA73 2SA75
A
standard software-function X X X X
B
positioner X X
C
process controller X
D
travel dependent output speed adjustment X X X
E
positioner + travel dependent output speed adjustment X X
F
external analog output speed setpoint X X X
G
positioner + external analog output speed setpoint X X
H
positioner with split-range functionality X X
J
travel dependent freely adjustable positioning times X X X
K
positioner + travel dependent freely adjustable positioning times X X
L
process controller + travel dependent freely adjustable positioning times X
4
round plug
Note: All set and parameterized values are stored in non-volatile memories (EEPROM)!
Signal assignment for the binary outputs
- for ECOTRON
(also refer to wiring diagrams, signals 1-5):
Signaling set (set 1 to 4 can be adjusted locally in the segment display of the actuator)
Output default setting
optional sets
with option „Y12“
Set 1 Set 2
Set 3
Set 4
1 Travel end OPEN NO End position OPEN NO End position OPEN NO Travel end OPEN NO
2 Travel end CLOSE NO End position CLOSED NO End position CLOSED NO Travel end CLOSE NO
3 Torque CL/OP reached NC Blinker NO Fault NC Ready+Remote NO
4 Ready+Remote NO Ready+Remote NO Local NO Torque OPEN reached NC
5 Warning motor temp. NC Warning motor temp. NC Warning motor temp. NC Torque CLOSE reached NC
NO = active high, NC = active low
- for PROFITRON (also refer to wiring diagrams, signals 1-8):
Optional free assignment of outputs,
NO/NC optional
(can be changed locally)
Output default setting with option „Y12“ with option „Y15“ with option „Y90“
1 End position OPEN NO Intermediate contact OP NO Intermediate contact OP NO Intermediate contact OP NO End position CLOSED
2 End position CLOSED NO Intermediate contact CL NO Intermediate contact CL NO Intermediate contact CL NO End position OPEN
3 Torque OPEN reached NC Ready+Remote NO Torque OPEN reached NO Torque OPEN reached NO Torque CLOSE reached
4 Torque CLOSE reached NC Torque OPEN reached NC Torque CLOSE reached NO Torque CLOSE reached NO Torque OPEN reached
5 Fault NC Torque CLOSE reached NC Ready+Remote NO
Local NC
Torque CL/OP reached
6 Local NO Local NO Local NO
Fault NC
Fault
7 Blinker NO Warning motor temp. NO Blinker NO
Not used
Blinker
8 Warning motor temp. NC Fault external voltage NC Warning motor temp. NO
Not used
Ready
Ready+Remote
NO = active high, NC = active low Local
Intermediate contact CL
Intermediate contact OP
Fault motor temperature
Warning motor temp.
Fault external voltage
Maintenance
Run indication CLOSE
Run indication OPEN
Run indication OPEN/CLOSE
Blinker+ End position CLOSED
Blinker+ End position OPEN

Related product manuals