EasyManua.ls Logo

AUMA SQ 14.2 - Page 3

AUMA SQ 14.2
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
236. Operation................................................................................................................................
236.1. Manual operation
236.1.1. Manual operation: engage
236.1.2. Manual operation: disengage
236.2. Motor operation
236.2.1. Local operation
246.2.2. Actuator operation from remote
267. Indications..............................................................................................................................
267.1. Indication lights
267.2. Mechanical position indicator/running indication
288. Signals.....................................................................................................................................
288.1. Feedback signals via output contacts (binary)
288.2. Feedback signals (analogue)
299. Commissioning (basic settings)...........................................................................................
299.1. Heat-up time for low temperature version
299.2. End stops in part-turn actuator
309.2.1. End stop CLOSED: set
319.2.2. End stop OPEN: set
319.3. Switch compartment: open
329.4. Torque switching: set
339.5. Limit switching: set
339.5.1. End position CLOSED (black section): set
339.5.2. End position OPEN (white section): set
349.6. Intermediate positions: set
349.6.1. Running direction CLOSE (black section): set
359.6.2. Running direction OPEN (white section): set
359.7. Test run
359.7.1. Direction of rotation: check
369.7.2. Limit switching: check
369.7.3. PTC tripping device (option): test
369.8. Electronic position transmitter EWG 01.1
379.8.1. Measuring range: set
389.8.2. Current values: adjust
389.8.3. LED end position signalling: switch on/off
399.9. Potentiometer
399.9.1. Potentiometer setting
399.10. Electronic position transmitter RWG
409.10.1. Measuring range: set
419.11. Mechanical position indicator: set
419.12. Switch compartment: close
4310. Commissioning – controls settings.....................................................................................
4310.1. Controls: open
4310.2. Type of seating: set
4410.3. Push-to-run operation or self-retaining: set
4510.4. Running indication (blinker transmitter): activate/deactivate
4510.5. Torque fault in collective fault signal: activate/deactivate
4510.6. Positioner
4610.6.1. Input ranges (signal type) for setpoint and actual value
4610.6.2. Behaviour on loss of signal (actuator reaction)
3
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Table of contents

Table of Contents

Related product manuals