236. Operation................................................................................................................................
236.1. Manual operation
236.1.1. Manual operation: engage
236.1.2. Manual operation: disengage
236.2. Motor operation
236.2.1. Local operation
246.2.2. Actuator operation from remote
267. Indications..............................................................................................................................
267.1. Indication lights
267.2. Mechanical position indicator/running indication
288. Signals.....................................................................................................................................
288.1. Feedback signals via output contacts (binary)
288.2. Feedback signals (analogue)
299. Commissioning (basic settings)...........................................................................................
299.1. Heat-up time for low temperature version
299.2. End stops in part-turn actuator
309.2.1. End stop CLOSED: set
319.2.2. End stop OPEN: set
319.3. Switch compartment: open
329.4. Torque switching: set
339.5. Limit switching: set
339.5.1. End position CLOSED (black section): set
339.5.2. End position OPEN (white section): set
349.6. Intermediate positions: set
349.6.1. Running direction CLOSE (black section): set
359.6.2. Running direction OPEN (white section): set
359.7. Test run
359.7.1. Direction of rotation: check
369.7.2. Limit switching: check
369.7.3. PTC tripping device (option): test
369.8. Electronic position transmitter EWG 01.1
379.8.1. Measuring range: set
389.8.2. Current values: adjust
389.8.3. LED end position signalling: switch on/off
399.9. Potentiometer
399.9.1. Potentiometer setting
399.10. Electronic position transmitter RWG
409.10.1. Measuring range: set
419.11. Mechanical position indicator: set
419.12. Switch compartment: close
4310. Commissioning – controls settings.....................................................................................
4310.1. Controls: open
4310.2. Type of seating: set
4410.3. Push-to-run operation or self-retaining: set
4510.4. Running indication (blinker transmitter): activate/deactivate
4510.5. Torque fault in collective fault signal: activate/deactivate
4510.6. Positioner
4610.6.1. Input ranges (signal type) for setpoint and actual value
4610.6.2. Behaviour on loss of signal (actuator reaction)
3
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1 Table of contents