EasyManua.ls Logo

AUMA SQ 14.2 - Measuring Range: Set

AUMA SQ 14.2
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Table 10: RWG 4020
2-wire system3-wire or 4-wire systemData
4 – 20 mA0 – 20 mA, 4 – 20 mAOutput current I
a
14 V DC + (I x R
B
), max. 30 V24 V DC (18 – 32 V)Power supply U
V
1)
20 mA24 mA at 20 mA output currentMax. current consumption
(U
V
– 14 V)/20 mA
600 ˖
Max. load R
B
0.1 %/V0.1 %/VImpact of power supply
0.1 %/100 ˖0.1 %/(0 – 600 ˖)
Load influence
< 0.3 ‰/KTemperature impact
–60 °C to +80 °CAmbient temperature
2)
5 k˖
Transmitter potentiometer
Power supply possible via: AC, AM controls or external power supply1)
Depending on temperature range of the actuator: Refer to name plate2)
Setting elements
The RWG is housed in the actuator switch compartment.The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
Setting is made via three potentiometers [1], [2] and [3].
Figure 29: View on control unit when switch compartment is open
[1] Potentiometer (travel sensor)
[2] Potentiometer min. (0/4 mA)
[3] Potentiometer max. (20 mA)
[4] Measuring point (+) 0/4 – 20 mA
[5] Measuring point (–) 0/4 – 20 mA
The output current (measuring range 0 – 20 mA) can be checked at measuring points
[4] and [5].
9.10.1. Measuring range: set
For measuring range setting, voltage must be applied at the position transmitter.
1. Move valve to end position CLOSED.
2. Connect ammeter for 0 – 20 mA to measuring points [4 and 5].
3. Turn potentiometer [1] clockwise to the stop.
4. Turn potentiometer [1] slightly in opposite direction.
5. Turn potentiometer [2] clockwise until output current starts to increase.
6. Turn potentiometer [2] in opposite direction until the following value is reached:
- for 0 – 20 mA approx. 0.1 mA
- for 4 – 20 mA approx. 4.1 mA
➥
This ensures that the signal remains above the dead and live zero point.
7. Move valve to end position OPEN.
8. Set potentiometer [3] to end value 20 mA.
40
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning (basic settings) AM 01.1

Table of Contents