5–43
DL MRX/MWX Communication Program (continued)
(Continued next page)
10
This rung checks to see if the drive Speed, Direction, External Fault, or Fault Reset
conditions have been changed in the local program, and need to be written to drive #1.
Drive #1
Direction New
V3002
=
Drive #1
Direction Retain
V3012
Drive #1
External Fault New
V3003
=
Drive #1
Ext Fault Retain
V3013
Drive #1
Fault Reset New
V3004
=
Drive #1
Fault Reset Retain
V3014
Drive #1
Speed Ref New
V3000
=
Drive #1
Speed Ref Retain
V3010
()
SET
Drive #1
Speed Ref
Write Enable
C10
Drive #1 Speed Ref
Write Enable
C10
Drive #1
Run CMD
Write Enable
C12
11
Drive #1
Direction, Fault, Reset
Write Enable
C11
Drive #1
Speed Ref
Write Enable
C10
MWX
CPU/DCM Slot:
Port Number:
Slave Address:
Function Code:
Start Slave Memory Address:
Start Master Memory Address:
Number of Elements:
Modbus Data type:
Exception Response Buffer:
CPU
K2
K1
06 - Preset Single Register
K42331
V3000
n/a
584/984 Mode
V5006
Port Busy
SP116
12
Drive #1
Direction, Fault, Reset
Write Enable
C11
Drive #1
Speed Ref
Write Enable
C10
MWX
CPU/DCM Slot:
Port Number:
Slave Address:
Function Code:
Start Slave Memory Address:
Start Master Memory Address:
Number of Elements:
Modbus Data type:
Exception Response Buffer:
CPU
K2
K1
16 - Preset Multiple Registers
K42333
V3002
K3
584/984 Mode
V5011
Port Busy
SP116
()
SET
Drive #1
Direction, Fault, Reset
Write Enabled
C11
()
SET
Drive #1, Speed,
Direction, Fault, Reset
Writes Finished
C13
This rung writes the new Speed Reference if it changes.
This rung writes the Direction, Ext Fault, and Fault Reset words if any of them changes.
Chapter 5: DURAPULSE MODBUS Communications
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013