Chapter 3: Keypad Operation and Quickstart
3–8
Acceleration Time Setting: 5.0
Range: 0.1 to 600 sec Default Setting: 10 sec
The motor should accelerate from 0 RPM to Maximum Motor RPM
(P0.04) in 5 seconds.
Deceleration Time Setting: 5.0
Range: 0.1 to 600 sec Default Setting: 30 sec
The motor should decelerate from 2000 rpm; Maximum Motor RPM
(P0.04) to 0 RPM in 5 seconds.
Volts/Hertz Settings Setting: 01
Range: 00 - General Purpose Default Setting: 0.0
01 - High Starting Torque
02 - Fans and Pumps
03 - Custom
The DURA
PULSE AC drive has some predefined torque settings that
meet the needs of most applications. A custom setting is available if
needed. In this example, the application requires a high starting
torque.
Source of Operation Command Setting: 02
Default Setting: 00
Settings 00 Operation Determined by Digital Keypad
01 Operation determined by external control
terminals. Keypad STOP is enabled.
02 Operation determined by external control
terminals. Keypad STOP is disabled.
03 Operation determined by RS-485 interface.
Keypad STOP is enabled.
04 Operation determined by RS-485 interface.
Keypad STOP is disabled.
The AC drive operation will be determined by external control
terminals, and the keypad stop will be disabled.
If parameter P3.00 = 00, 01, or 03, enabling the keypad STOP key, the drive will stop if
the keypad is removed from the drive.
P3.00
P2.00
P1.02
P1.01
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013