3–9
Source of Frequency Command Setting: 02
Default: 01
Settings: 01 Frequency determined by digital keypad up/down
02* Frequency determined by 0 to +10V input on AI1
terminal.
03 Frequency determined by 4 to 20 mA input on AI2
terminal.
04 Frequency determined by 0 to 20 mA input on AI2
terminal.
05 Frequency determined by RS-485 communication
interface
06 Frequency determined by-10V~+10V input on AI3
terminal
* In order to set P4.00 = 02, you must first change the value of P4.13 to
some value other than two (02) in order to avoid the “Error: Duplicate
Function” error message. (P4.13 default value is 02)
Electronic Thermal Overload Relay Setting: 00
Default: 00
Settings: 00 Constant Torque (inverter/vector duty motor)
01 Variable Torque (fan-cooled standard motor)
02 Inactive
This function setting 00 is the standard overload protection curve used
to protect inverter/vector duty motors.
User Defined Display Function Setting: 01
Default Setting: 00
Settings: 00 Output Frequency (Hz)
01 Motor Speed (RPM)
02 Scaled Frequency
03 Output Current (A)
04 Motor Load (%)
05 Output Voltage(V)
06 DC Bus Voltage (V)
07 PID Setpoint
08 PID Feedback (PV)
09 Frequency Setpoint
The AC drive display will default to motor speed (rpm) when running.
P6.00
P8.00
P4.00
Chapter 3: Keypad Operation and Quickstart
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013