Chapter 4: AC Drive Parameters
4–14
Encoder Feedback Parameters
P10.00
Encoder Pulses per Revolution 01 to 20000 1024
P10.01
Encoder Type Input
00: Disable
01: Single Phase
02: Quadrature, FWD - CCW
03: Quadrature, FWD - CW
00
P10.02
Proportional Control 0.0 to 10.0 1.0
P10.03
Integral Control 0.00 to 100.00 sec 1.00
P10.04
Encoder Control Output Limit 0.0 to 20.0% 7.5
P10.05
Encoder Loss Detection
00: Warn and continue operation
01: Warn and RAMP to stop
02: Warn and COAST to stop
00
* Some parameters and settings are available only in later firmware versions of DURAPULSE drives. Refer to
the beginning of this “DURA
PULSE Parameter Summary” section for more information.
Parameter can be set during RUN Mode.
Parameter Summary (continued)
Parameter
*
Description Range*
Default
Setting
User
Setting
Communications Parameters (continued)
P9.42
Manufacturer Model Information
00: GS3-21P0 (230V 3ph 1.0hp)
01: GS3-22P0 (230V 3ph 2.0hp)
02: GS3-23P0 (230V 3ph 3.0hp)
03: GS3-25P0 (230V 3ph 5.0hp)
04 :GS3-27P5 (230V 3ph 7.5hp)
05: GS3-2010 (230V 3ph 10hp)
06: GS3-2015 (230V 3ph 15hp)
07: GS3-2020 (230V 3ph 20hp)
08: GS3-2025 (230V 3ph 25hp)
09: GS3-2030 (230V 3ph 30hp)
10: GS3-2040 (230V 3ph 40hp)
11: GS3-2050 (230V 3ph 50hp)
12: GS3-41P0 (460V 3ph 1.0hp)
13: GS3-42P0 (460V 3ph 2.0hp)
14: GS3-43P0 (460V 3ph 3.0hp)
15: GS3-45P0 (460V 3ph 5.0hp)
16: GS3-47P5 (460V 3ph 7.5hp)
17: GS3-4010 (460V 3ph 10hp)
18: GS3-4015 (460V 3ph 15hp)
19: GS3-4020 (460V 3ph 20hp)
20: GS3-4025 (460V 3ph 25hp)
21: GS3-4030 (460V 3ph 30hp)
22: GS3-4040 (460V 3ph 40hp)
23: GS3-4050 (460V 3ph 50hp)
24: GS3-4060 (460V 3ph 60hp)
25: GS3-4075 (460V 3ph 75hp)
26: GS3-4100 (460V 3ph 100hp)
## N/A
DURAPULSE AC Drive User Manual