4–23
DC Injection Current Level Default Setting: 00
Range: 00 to 100%
This parameter determines the amount of DC Braking Current applied to the
motor during start-up and stopping. When setting DC Braking Current, please
note that 100% is equal to the rated current of the drive. It is recommended to
start with a low DC Braking Current Level and then increase until proper holding
torque has been attained.
DC Injection during Start-up Default Setting: 0.0
Range: 0.0 to 5.0 sec
This parameter determines the duration of time that the DC Braking Current will
be applied to the motor during the AC drive start-up. DC Braking will be applied
for the time set in this parameter until the Minimum Frequency is reached during
acceleration.
DC Injection during Stopping Default Setting: 0.0
Range: 0.0 to 25.0 sec
This parameter determines the duration of time that the DC braking voltage will
be applied to the motor during stopping. If stopping with DC Braking is desired,
then P1.00 must be set to Ramp to Stop (00).
Start-point for DC Injection Default Setting: 0.0
Range: 0.0 to 60.0 Hz
This parameter determines the frequency when DC Braking will begin during
deceleration.
Operation
Command
Min. Output
Frequency
Start-Point for DC Braking
time
DC Injection Current Level
Master
Frequency
ON OFF
P 1.22
P 1.20
P 1.21
P 1.18
P1.22
P1.21
P1.20
P1.18