2 Specifications
18 © Copyright Reserved Autonics Co., Ltd.
Series CTS CTY CTM
Model
1-stage preset
CT4S-1P□□
CT6S-1P□□ CT6Y-1P□□ CT6M-1P□□
2-stage presert
CT4S-2P□□
CT6S-2P□□ CT6Y-2P□□ CT6M-2P□□
Indicator
-
CT6S-I□□ CT6Y-I□□ CT6M-I□□
Standard Comm. Standard Comm. Standard Comm.
Control
output
Contact
(Relay)
Type
1-stage
SPDT(1c): 1 SPDT(1c) : 1 SPDT(1c) : 1
2-stage
SPST(1a): 2
SPST
(1a): 1,
SPDT
SPST
(1a): 2
SPST(1a): 1,
SPDT(1c): 1
Capacity
250VAC 5A resistive load
250VAC 3A
resistive load
250VAC 5A
resistive load
Solid
state
(NPN
open
collector)
Type
1-stage
1
-
1
1 2
2
2-stage
-
3
Capacity
Max. 30VDC, 100mA
External power supply
Max. 12VDC ±10%, 100mA
Memory retention Approx. 10 years (non-volatile memory)
Insulation resistance
Over 100MΩ (at 500VDC megger)
Dielectric strength 2,000VAC 50/60Hz for 1 min
Noise
immunity
AC voltage
Square-wave noise by noise simulator (pulse width 1µs) ±2kV
AC/DC voltage
Square-wave noise by noise simulator (pulse width 1µs) ±500V
Vibration
Mechanical
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each
X, Y, Z direction for 1 hour
Malfunction
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z
direction for 10 minutes
Shock
Mechanical
300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Malfunction
100m/s² (approx. 10G) in each X, Y, Z direction for 3 times
Relay
life cycle
Mechanical Min. 10,000,000 operations
Malfunction Min. 100,000 operations
Protection structure Front part: IP65 (IEC standards)
Environ-
ment
Ambient temp.
-10 to 55℃, storage: -25 to 65℃
Ambient humi. 35 to 85% RH, storage: 35 to 85% RH
Approval
Weight
※1
Approx. 212g
(approx. 159g)
Approx. 228g
(approx. 140g)
Approx. 322g
(approx. 252g)
※
1: The weight includes packaging. The weight in parentheses is for unit only.
※
Environment resistance is rated at no freezing or condensation.