2.4.4 Parameter 3 Setting Group [Func: 03/06/16, RW:
R/W]
40151(0096)
IN-T
Input Type
See the turn of input specifications
-
TCk1
40152(0097)
UNIT
Sensor Temperature Unit
0: ?C 1: ?F
-
?C
40153(0098)
L-RG
Analog Low-limit Input Value
Minimum Range~ H-RG - F.S10%
Digit
00)0
40154(0099)
H-RG
Analog High-limit Input Value
L-RG+F.S10%~Maximum Range
Digit
10)0
40155(009A)
DOT
Scale Value Decimal Point
0: 0 1: )0 2: )00 3: )000
-
)0
40156(009B)
L-SC
Low Scaling
F.S
-
00)0
40157(009C)
H-SC
High Scaling
F.S
-
10)0
40158(009D)
dUNT
Display Unit
0: ?C 1: ?F 2: ?/O 3: OFF
-
?C
40159(009E)
IN-B
Input Bias
-999~999: -999~0999
-1999~9999: `9(9~99(9
Digit
0000
40160(009F)
MAvF
Moving Average Filter
1~1200: 00)1~12)0
Sec.
00)1
40161(00A0)
L-SV
SV Low-limit Set Value
Input Low-limit Value(L-SC) ~ H-SV-1Digit
℃/℉
%F.S
-200
00)0
40162(00A1)
H-SV
SV High-limit Set Value
L-SV+1Digit ~ Input High-limit Value(H-SC)
℃/℉
%F.S
1350
10)0
40163(00A2)
O-FT
Control Output Operation
Mode
Standard Type 0: HEAT 1: COOL
-
HEAT
Heating &
Cooling Type
0: HEAT 1: COOL 2: H-C
-
H-C
40164(00A3)
C-MD
Temperature Control Type
Mode
0: PID 1: ONOF
-
PID
Control Mode
0: pP 1: Pon 2: OnP
3: OnON
-
pP
40165(00A4)
ATT
Auto-tuning Mode
0: TUN1 1: TUN2
-
TUN1
40166(00A5)
OUT1
OUT1 Control Output Type
0: SSR 1: CURR
-
SSR
40167(00A6)
O!SR
OUT1 SSR Output Type
0: STND 1: CYCL 2: PHAS
-
STND
40168(00A7)
O!MA
OUT1 Current Output Range
0: 4-20 1: 0-20
-
4-20
40169(00A8)
OUT2
OUT2 Control Output Type
0: SSR 1: CURR
-
SSR
40170(00A9)
O@MA
OUT2 Current Output Range
0: 4-20 1: 0-20
-
4-20
40171(00AA)
H-T
Heating Control Time
1~1200: 00)1~2)0
Sec.
02)0
40172(00AB)
C-T
Cooling Control Time
1~1200: 00)1~12)0
Sec.
02)0
40173~40200 Reserved