4output frequencies: F = Fo + ΔF
ΔF =Kp×En+1- En+ Ki×En+1 + Kd×En+1 - 2En + En-1
Fo=20 Kp=6.0, Ki=8.0, Kd=2.0 (EEEPROM can adjust)
a .Frequency range: 20Hz85Hz,if F20Hz 20Hz is the bottomif F85Hz85 Hz is the
top.
b. En+1=Tr-TsEn+1 range: -3 +13
c. If consecutive time of En+1-2 is 2min,the compressor will be shut down.
d. Starting with power, if En+10,the compressor won’t work, if En+10,the compressor will
open.
e. There are no temperature compensation for the firstly open, when the compressor start, it
will be Tr temperature compensation, for example, compensate with 2, the Tr=Trtrue+2.
f. when the compressor shut down, the indoor fan will still running according to the setting
wind.
The above is the work frequency without any other restrictions on high-frequency and
protections on down-frequency; if there are restrictions and protections, the frequency vale
will adjust on the above value, and the adjust value according to the certain mode and the
fault protection instructions.
5In cooling mode, it can set as automatic wind, high wind, medium wind, low wind to meet
requirement, and the automatic wind speed can controlled as follows
when TrTs+ 3,High wind
when Ts+1Tr<Ts +3 ,Medium wind
when TrTs+ 1,low wind
At automatic speed, when the wind speed from low switching high, the wind speed without
delay; while from high switching low, there will be delay with 3 min.
6The functions of this model are as follows: time setting, sleep, auto start, Anion, high
efficiency
7According to cooling operation, there are anti-freeze protection of indoor coil , temperature
thermal protection of outdoor exhaust, over-current protection, overheating protection of
compressor, fault protection of indoor fan , sensor fault protection, fault protection of module,
fault protection of communication, 3min delay protection of compressor.
8First start with power without 3 min delay protection.
9The order of on/off of Outdoor fan and compressor: The compressor will open 5s later after
outdoor fan open and the outdoor fan will shut down 15s later after the compressor shut down.
10The restrictions and protection for Ta when cooling.
When Ta47,it open as cooling mode normal, the maximum work frequency of
23

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUX ASW-H09A4/SAR1DI and is the answer not in the manual?

AUX ASW-H09A4/SAR1DI Specifications

General IconGeneral
BrandAUX
ModelASW-H09A4/SAR1DI
CategoryAir Conditioner
LanguageEnglish

Related product manuals