34
output negative ion; In case that Negative ion function is started, press the Negative ion
function button on the remote control, negative ion electrical apparatus on the controller
close, he whole machine will not output negative ion
14. “I Feel” Function
1Enter method
press”I Feel” function button on the remote control, when controller receives signal, then
enter”I Feel” function, at this time, controller will treat the temperature for sensor on the
remote control as Tr on the original controller to deal (including the time of intelligent
defrost) temperature compensation is still effective, frequency will still be counted as
according formula.
2Remote control towards the receiving window for controller, remote control will lunches a
signal every 3min after”I Feel” function starts up.
3When”I Feel” function is starting up, main control board will not check the original Tr
sensor on controller.
4Quitting methods
a)press”I Feel” function button one more tine, this function will be cancelled.
b)If controller can not receive the signal for remote control wthin 10min , “I Feel” function will
be cancelled automatically, Tr will re-control as the temperature that Tr sensor on controller
checks
15. Testing under Rated Work
1Refrigerating rated testing
high wind and temperature 18 C are set , receive signal for sleeping button 8 times
continuously within 8s, if refrigerating rated testing function is set successfully, buzzer will
sound four times, system enter rated testing status, compressor will run as fixed frequency
54Hz, if any one condition above does not work, rated frequency running will quit.
2Heating rated testing
high wind and temperature 30 C are set , receive signal for sleeping button 8 times
continuously within 8s, if refrigerating rated testing function is set successfully, buzzer will
sound four times, system enter rated testing status, compressor will run as fixed frequency
60Hz, if any one condition above does not work, rated frequency running will quit.
16. The Lowest Frequency Testing
1Refrigerating rated testing refrigerating rated testing
high wind and temperature 18 C are set , receive signal for sleeping button 12 times
continuously within 8s, if refrigerating rated testing function is set successfully, buzzer will
sound four times, system enter the lowest frequency testing status, compressor will run as the
lowest frequency 30Hz, if any one condition above does not work, the lowest frequency
testing running will quit.
2Heating rated testing
high wind and temperature 30 C are set , receive signal for sleeping button 12 times
continuously within 8s, if refrigerating rated testing function is set successfully, buzzer will
sound four times, system enter the lowest frequency testing status, compressor will run as the
lowest frequency 30Hz, if any one condition above does not work, the lowest frequency
testing running will quit.
17. High Efficiency Running
High efficiency running only suits for two models: refrigerating and heating.
1Main control board receives high efficiency on remote control and enters high efficiency
Refrigerating: frequency 85Hz, wind speed too high (1130r/min)Heating: frequency
85Hz, wind speed too high (1130r/min), preventing cold wind function is still effective
2time >15min high efficiency stops
3all limiting and protecting terms work during the time of high efficiency

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUX ASW-H09A4/SAR1DI and is the answer not in the manual?

AUX ASW-H09A4/SAR1DI Specifications

General IconGeneral
BrandAUX
ModelASW-H09A4/SAR1DI
CategoryAir Conditioner
LanguageEnglish

Related product manuals