b)、When 25 ≤Te℃ <30 ,indoor motor run at the lower wind speed as soon as it ℃
operates.If Te still at upper trend ,it should be Te<30 and indoor motor blow lower ℃
wind speed;
c)、When 30 ≤Te℃ <38 ,indoor motor run at the low wind speed;℃
d)、When Te≥38 ,indoor motor run at the ℃ setting wind speed;
When Te go down:
a)、When Te≥34 ,indoor motor run at the ℃ setting wind speed;
b)、When 28 ≤Te℃ <34 ,indoor motor run at the low wi℃ nd speed;
c)、When 23℃<Te <28 ,indoor motor run at the lower wind speed;℃
d)、When Te≤23 ,indoor motor stop to run ;℃
When compressor stop to run:
a)、When Te go down and Te>25 ,indoor motor blow the lower wind speed;Or when ℃
Te≤25 ,indoor motor shut down;℃ ℃
b)、When Te go up and Te≥28 ,indoor motor blow the lower wind speed;Or when Te℃ <
28 ,indoor motor shut down;℃
12、Compare to protect the Ta(Indoor temperature) at the heating mode
When Ta≥22 ,it’s able to run at the heating mode and the highest working frequen℃ cy of
compressor is 50Hz;
When 22℃>Ta≥10 ,it’s able to run at the heating mode and the the highest working ℃
frequency of compressor is 70Hz;
When Ta<10 ,it’s able to run at the heating mode and the the highest working frequency of ℃
compressor is 80Hz;
13、Intelligent anti-frost
1、Condition for anti-frost:
When the outdoor sensor’s at the good condition and meet the following condition,it start to
function:
1)When compressor run over 45min,mode change or shut down and the cumulate time
26