Chapter 4. Explanation of Operation
  Example sequence
 z Normal operation (Non-recycling gas-fired combustion)
Input AUR890 operation Sequence 
codes
Operation of external devices
Power ON When approximately 8 seconds have passed after the power has been 
turned on, the 7-segment LED display on the front panel of the AUR890 
shows the sequence code [- -].
- -
Burner 
operation 
switch ON
- - When the burner operation switch is turned 
on, the blower starts to operate, and if the 
limit and interlock conditions are normal, a 
prepurge is done. After the prepurge, the 
prepurge completion signal is turned ON.
Blower: operating
Controller 
ON
If the prepurge completion signal is ON and the controller is ON, the 
internal circuits are checked during the start check.
P 1
Afterward a false ame check is conducted during the ignition wait 
time.
P3
If the status is normal, the lockout time begins, relays K1, K2, K3 and K5 
turn ON, the ignition transformer starts, the pilot valve begins to open, 
and external timer TM1 turns ON.
P4
Ignition transformer : start
Pilot valve : open
(TM1 starts)
When the ame detector detects the pilot burner ame, relay K5 turns 
OFF to stop the ignition transformer.
P5
Ignition transformer : continues operation
Pilot valve : remains open
Relay K4 and external relay 103X turn ON.
When the time set for timer TM1 has passed and TM1's contacts have 
turned ON, the main valve opens to begin normal combustion.
The FLAME LED (green) on the front panel of the AUR890 lights up.
P8
Ignition transformer : stop
Main valve : open
(103X : ON)
(TM1's contacts : ON)
Burner 
operation 
switch OFF
When the burner operation switch is turned OFF, relays K1, K2, K3 and 
K4 turn o, and the pilot and main valves begin to close.
The FLAME LED (green) on the front panel of the AUR890 turns o.
- - Fuel oil combustion valve : closed
Main valve : closed
Blower : stop
Power OFF When the power is turned OFF, the 7-segment LED display on the front 
panel of the AUR890 stops showing the sequence code [- -].
*   The AUR890 turns the main valve ON after the standby process for normal combustion. This feature does not allow the main valve to 
be turned on immediately after ignition in order to prevent the flame from being blown out. During the standby process for normal 
combustion, if the time set for external timer TM1 has passed and the contacts are reversed, the supply of power to the pilot valve and 
main valve may be interrupted for a moment. 
Whenever a flame is detected just before completion of the time set for external timer TM1, ignition is delayed. Adjust the burner so that 
it ignites reliably at least one second before the time set for external timer TM1 passes.
––
P1
–– ––
[Input]
Power supply
[7-segment display]
Limit, Interlock
Stop
Start check
P3
Ignition standby
P4
Lockout timing
P8
Main burner combustion standby
P5
RUN
Stop
[Output]
Ignition transformer
Burner operation switch
Blower
Controller
Flame signal
RESET switch
[LED]
FLAME LED (Green)
Alarm output
Pilot valve
AUR890
Main valve
ALARM LED (Red)
Prepurge time
(external circuit)
Start check + Ignition standby time
Approximately 3 s
Approximately 8 s
Lockout timing time
Main burner combustion standby time
TM1 on delay time