Parameter Descriptions 7-25
t59 Communication protocol select
Range: 0=Modbus RTU
1=LS BUS
Default: 0
Access Configurable
See Also: t60-t61, t64-t81
Sets the protocol for the serial communication network.
t60 Inverter Number
Range: 1-250
Default: 1
Access Tunable
See Also: t59, t61, t64-t81
Sets the drive node address for the RS485 port multi-drop network.
t61 Baud Rate
Range: 0=1200 [bps]
1=2400 [bps]
2=4800 [bps]
3=9600 [bps]
4=19200 [bps]
Default: 3
Access Tunable
See Also: t59-t60, t64-t81
Selects the Baud Rate of RS485 Communication.
t62 Frequency Loss Mode
Range: 0=Continue operation at last frequency command
1= Coast to Stop.
2= Decelerate to stop.
Default: 0
Access Tunable
See Also: P40, t35, t63
When the frequency reference is from the Analog Input or RS485 Port, this
parameters sets the action to take if the speed reference is lost.