Balluff Network Interface EtherCAT
www.balluff.com
16
5 Integration
Configuring IO-
Link module
BNI ECT-508-105-Z015 is a modular device. The following slot structure is present:
Slot
number
Meaning
1-8
IO-Link ports
9-16
Unused slots, reserved for future expansions
17
Input pin 2
18
Short circuit pin 2
19
Short circuit pin 4
20
Sensor short circuit
21
Module status
22-32
Unused slots, reserved for future expansions
33
Output pin 2
34
Restart Pin 2
35
Restart Pin 4
36
Display LEDs
The slots for future expansions are not used. A number of process data (buffer size) can be
assigned to the other slots. Unused slots may remain empty and then are not transferred as
cyclical process data.