6 Process Data
6.2. Process Data
Outputs
There are 134 bytes of output data. Have a look at the tables below to see the mapping of
the process data outputs.
Byte
Modul part
Description
05
Standard I/O ports
Process data outputs on standard Inputs
6…37
IO-Link Port 1
Process data outputs on IO Link Port 1
3869
IO-Link Port 2
Process data outputs on IO Link Port 2
70101
IO-Link Port 3
Process data outputs on IO Link Port 3
102…133
IO-Link Port 4
Process data outputs on IO Link Port 4
Standard Output
Data
Byte
Bit
Description
7
6
5
4
3
2
1
0
0
O32
O34
O22
O24
O12
O14
O02
O04
Output data
O04
Output on port 0 pin 4
To use this function on a IO Link
port the port must be configured
as an output (see 0- Module
Configuration)
1
O72
O74
O62
O64
O52
O54
O42
O44
2
R32
R34
R22
R24
R12
R14
R02
R04
Restart
Restart output here after a
detected short-circuit
3
R72
R74
R62
R64
R52
R54
R42
R44
4
0
0
0
0
0
0
0
0
Reserved
5
0
0
0
0
0
DL
GO
RO
Display Control
DL: Display lock / PLC lock
GO: Green LED on Display on
RO: Red LED on Display on
IO Link Output
Data
Byte
Bit
Description
7
6
5
4
3
2
1
0
6
37
IO Link Port 1 Output data
The data of the other IO Link ports has the same structure and follows here