7
3 Getting Started
I/O-Port
M12, A-coded, female
Pin
Function
1
+24V, 200mA
2
Input / Output
3
GND
4
Input / Output
5
FE
Note!
For the digital sensor inputs follow the input guideline per EN61131-2, type 2.
Note!
Each output serves a maximum current of 1,6 amperes. Total current of the
module has to be lower than 9 amperes.
Note!
Unused I/O port socket must be fitted with cover caps to ensure IP67 protection
rating.
IO Link-Port
M12, A-coded, female
Pin
Function
1
+24V, 1,6 A
2
Input / Output
3
GND
4
IO Link / Input / Output
5
n.c.