BPM 200 - 300 - 350
1 Gas solenoid valve
2 Maximum pressure adjustment screw (rotate counter-clockwise
to increase and clockwise to decrease)
3 Minimum pressure adjustment screw (counterclockwise to incre-
ase, clockwise to decrease)
4 Gas inlet
5 Gas inlet pressure port
On models BPM 200-300-350 EVO the gas train is not connected to
burner.
The connection is made by screwing the union (7) (supplied) to the
respective anges (2) (8).
Subsequently connect the 4 mm diameter gas compensation pipe
(3) supplied by inserting it into the quick couplings 1 and 4 installed
in the Air Venturi (6) and in the gas valve (5).
After this operation is completed, test gas train for leakage.
DANGER / ATTENTION
Failed connection of the compensation tube (3) will cause bur-
ner operating anomalies.