Manual 2100-746
Page 21 of 55
Lead/Lag Rotation
Pressing the Advance Lead button on the home
screen will cause the lead to advance to the next unit.
This may be useful during service and maintenance
procedures.
Lead unit will be determined by an internal timer and
Lead-Lag Changeover Time selected by user. The Lead-
Lag Changeover Time will be configurable with a range
of 1 to 30 days and can be disabled by setting duration
to 0 for an overall range of 0 to 30. Default setting
for Lead-Lag will be 7 days. Lead unit will rotate after
Lead-Lag Changeover Time expires. At expiration, the
lead unit will rotate to the next available unit (Example:
1 to 2) and once the last address used expires the
lead unit will restart at unit 1. Lead-Lag configuration
will apply to both heating and cooling. If disabled by
setting to 0, the lead unit will only rotate manually by
utilizing the Advance Lead button. Humidification and
dehumidification will not rotate lead. The lead unit will
always be unit 1. This will allow users to mix dehum
and non-dehum units in a single application. (Dehum
units will need to be placed in the lowest unit address
locations, i.e., unit 1 will always be the first dehum
unit when installed for use with the MC5300/5600.)
Number of units used for Lead-Lag will be determined
by user configurable setting in the Setup Menu.
When Lead-Lag Changeover Time expires and lead unit
is shifted, the call will be satisfied and then the lead
unit will rotate. If the Advance Lead button is used to
rotate the lead unit, the call will end, the lead unit will
be shifted and units will restage in accordance with the
demand.