Set Point (SP) or Item Name Current Range Default User Settings
Auxiliary Out Configuration
Emergency Off, Gen Run, High Humidity
Alarm, Dust Alarm or Dehum Active
Emergency
Off
System Setup Items
Languages English, French or Spanish English
Password Protection Yes or No No
Staging Logic Alternating or Non-Alternating Alternating
Lead/Lag Changeover Time 0 – 30 Days 0 = Disable 7 Days
Continuous Blower Logic Lead, All, None, Pre-Purge or Custom None
Pre-Purge 1 – 5 Minutes 1 Minute
Degrees Fahrenheit or Celsius Fahrenheit
Temperature Sensor Logic Average, Highest or Lowest Average
REM 1 Temperature Sensor Indoor Temperature or Not Connected
Not
Connected
REM 2 Temperature Sensor
Indoor Temperature, Outdoor Temperature or
Not Connected
Not
Connected
Minimum Run Time 0 – 5 Minutes 3 Minutes
Maximum Number of Units
While in Generator Mode
1 − 6 Units 1
Touch Screen Display Brightness 10 − 100% 80%
Time Settings
Hour 1 – 12
Minute 0 – 59
AM or PM AM or PM
Date Settings
Month 1 – 12
Day 1 – 31
Year 2000 – 2999
Sensor Calibration Values
Local Temperature -15 – 15°F 0
Local Humidity -15 – 15% RH 0
Remote 1 -15 – 15°F 0
Remote 2 -15 – 15°F 0
TABLE 1
MC5000 Series Set Points/Defaults/User Settings Record (cont.)
Manual 2100-746
Page 23 of 55