7960-788
Revised: 2-13-17 Commissioning Report Page 3 of 3
Outdoor Ambient Temperature
Indoor Room Temperature
Controller Setup – Verify the following:
Yes No Are all hard wired alarms (NOC) and/or Ethernet cable connected and functional?
Yes No Are all remote indoor temperature and humidity sensors connected and operational?
Yes No Is the time and date set in the controller?
Yes No
Warm the indoor temperature and humidity sensor with a blow dryer or heat gun. Be
careful not to overheat and damage the sensor. Do all units operate?
Yes No Clear all alarms in the controller. Do all alarms stay inactive (alarms clear)?
Yes No Are the supply and return grilles the correct model for the product?
Yes No Are all supply grille fins adjusted to force air towards the room floor?
Record indoor temperature displayed on the controller.
Record indoor humidity displayed on the controller.
Power Supply Voltage at unit controller measured with Multimeter.
Controller Software Version:
Final Jobsite review – Verify the following:
Are all installation tools including driver bits, pliers, and screwdrivers accounted for?
Yes No Are all HVAC unit panels secured including control panel, filter, and front doors?
Yes No Are all alarms cleared from the controller?
Yes No If the site is monitored, have external parties received notification the job is complete?
Trained installers and contractors are eligible for an extended warranty. Go to www.bardhvac.com
and select “Distributor Access”. Log into the extended warranty program using your username and
password provided at the end of the training class.
Standard warranty registration is available at www.bardhvac.com under “Warranty Registration”.
When completed, store this document in the shelter with manuals for future reference.
3D Barcode for Extended Warranty 3D Barcode for Standard Warranty