EasyManuals Logo

Basler DECS-100 User Manual

Basler DECS-100
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
6-4 DECS-100 Maintenance and Troubleshooting 9287500991 Rev K
Step 2. Verify that the sensing potential transformer (if used) has the correct turns ratio.
If the turns ratio of the sensing potential transformer is incorrect, replace the sensing potential
transformer with the correct one.
If the sensing potential transformer is correct, proceed to Step 3.
Step 3. High generator output voltage may occur when operating in droop mode with a capacitive load.
If the high voltage condition is not caused by the droop function, proceed to Step 4.
Step 4. Verify that the voltage setpoint is not being modified by application of voltage to the optional
Accessory Input.
If the high voltage condition is not caused by voltage applied to the Accessory Input, proceed to
Step 5.
Step 5. Replace the DECS-100 unit.
Poor Voltage Regulation
Step 1. Verify that the case of the DECS-100 is properly grounded.
If the DECS-100 is not properly grounded, connect a dedicated ground wire to the quarter-inch
fast-on connector labeled GND on the rear of the DECS-100 case.
If the DECS-100 is properly grounded, proceed to Step 2.
Step 2. Check for grounded field leads.
If the field leads are grounded, isolate them from ground.
If the field leads are not grounded, proceed to Step 3.
Step 3. If the DECS-100 is powered from a PMG, check for grounded PMG leads.
If the PMG leads are grounded, isolate them from ground.
If the PMG leads are not grounded, proceed to Step 4.
Step 4. Verify that the generator frequency is not dropping below the DECS-100 underfrequency
setpoint when load is applied to the generator.
If the generator frequency is dropping below the underfrequency setpoint, reduce the setpoint if
possible. Also check the prime mover and generator for proper sizing in relation to the applied
load.
If poor regulation is not related to DECS-100 underfrequency operation, proceed to Step 5.
Step 5. Verify that regulation is not being affected by normal droop operation.
If droop operation is not affecting regulation, proceed to Step 6.
Step 6. Replace the DECS unit.
Generator Output Unstable (Hunting)
Step 1. Verify that the governor for the prime mover is operating properly.
If the governor is not operating properly, troubleshoot using the manufacturer's suggested
procedures.
If the governor is operating properly, proceed to Step 2.
Step 2. Verify that the sensing and input power leads are connected securely.
If the sensing or input power leads are not connected securely, tighten the connections.
If the sensing or input power lead connections are secure, proceed to Step 3.
Step 3. Verify that the DECS-100 Stability Range is set to the proper range.
If the Stability Range setting is incorrect, reset the Stability Range.
If the Stability Range setting is correct, proceed to Step 4.
Step 4. Verify that the Stability Level is properly set.
If the Stability Level is not properly set, reset the Stability Level.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler DECS-100 and is the answer not in the manual?

Basler DECS-100 Specifications

General IconGeneral
BrandBasler
ModelDECS-100
CategoryControl Systems
LanguageEnglish

Related product manuals