27-4 9440300990
CAN Communication DECS-250
Table 27-2. Diagnostic Information Obtained Over CAN Bus Interface 2
PGN
Name
0xEA00
Request DTCs
0xFECA
Currently Active DTCs
0xFECB
Previously Active DTCs
0xFECC
Clear Previously Active DTCs
0xFED3
Clear Active DTCs
Table 27-3. Reported DTCs
SPN hex (decimal)
Name
FMI hex (decimal) *
0x263 (611)
Loss of Sensing Fault
0x00 (0)
0x264 (612)
EDM Fault
0x0E (14)
0xD34 (3380)
Field Overvoltage Fault
0x00 (0)
0xD35 (3381)
Field Overcurrent Fault
0x00 (0)
0x988 (2440)
Overvoltage Fault
0x0F (15)
0x988 (2440)
Undervoltage Fault
0x11 (17)
0x998 (2456)
Loss of Excitation Fault
0x11 (17)