DECS-250 PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
FCR Setpoints
70
Float
R/W
Excitation Current
Preposition 3 GG
Amp
0 - 12
FVR Setpoints
71
UINT32
R/W
Excitation Voltage
Preposition
Mode 1 GG
No Unit
Maintain=0 Release=1
FVR Setpoints
71
UINT32
R/W
Excitation Voltage
Preposition
Mode 2 GG
No Unit
Maintain=0 Release=1
FVR Setpoints
71
UINT32
R/W
Excitation Voltage
Preposition
Mode 3 GG
No Unit
Maintain=0 Release=1
FVR Setpoints
72
Float
R/W
Excitation Voltage Traverse
Rate GG
Sec
10 - 200
FVR Setpoints
72
Float
R/W
Excitation Voltage Setpoint
GG
V
0 - 75
FVR Setpoints
72
Float
R/W
Excitation Voltage Min
Setpoint
Limit GG
%
0 - 150
FVR Setpoints
72
Float
R/W
Excitation Voltage Max
Setpoint
Limit GG
%
0 - 150
FVR Setpoints
72
Float
R/W
Excitation Voltage
Preposition 1 GG
V
0 - 75
FVR Setpoints
72
Float
R/W
Excitation Voltage
Preposition 2 GG
V
0 - 75
FVR Setpoints
72
Float
R/W
Excitation Voltage
Preposition 3 GG
V
0 - 75
VAR Setpoints
73
UINT32
R/W
Gen Var Preposition
Mode1 GG
No Unit
Maintain=0 Release=1
VAR Setpoints
73
UINT32
R/W
Gen Var Preposition
Mode2 GG
No Unit
Maintain=0 Release=1
VAR Setpoints
73
UINT32
R/W
Gen Var Preposition
Mode 3 GG
No Unit
Maintain=0 Release=1
VAR Setpoints
74
Float
R/W
Sys Option Fine Adjust
Band GG
%
0 - 30
VAR Setpoints
74
Float
R/W
Gen Var Traverse
Rate GG
Sec
10 - 200
VAR Setpoints
74
Float
R/W
Gen Var Setpoint GG
kvar
0 41.57
VAR Setpoints
74
Float
R/W
Gen Var Min Setpoint
Limit GG
%
-100 - 100
VAR Setpoints
74
Float
R/W
Gen Var Max Setpoint
Limit GG
%
-100 - 100
VAR Setpoints
74
Float
R/W
Gen var
Preposition 1 GG
kvar
0 41.57
VAR Setpoints
74
Float
R/W
Gen var
Preposition 2 GG
kvar
0 41.57
VAR Setpoints
74
Float
R/W
Gen var
Preposition 3 GG
kvar
0 41.57
PF Setpoints
75
UINT32
R/W
Gen PF Preposition
Mode 1 GG
No Unit
Maintain=0 Release=1
PF Setpoints
75
UINT32
R/W
Gen PF Preposition
Mode 2 GG
No Unit
Maintain=0 Release=1
PF Setpoints
75
UINT32
R/W
Gen PF Preposition
Mode 3 GG
No Unit
Maintain=0 Release=1
PF Setpoints
76
Float
R/W
Gen PF Traverse Rate GG
Sec
10 - 200
PF Setpoints
76
Float
R/W
Gen PF Setpoint GG
PF
0.5 – -0.5
PF Setpoints
76
Float
R/W
Gen PF Min Setpoint
Limit GG
PF
0.5 – 1
PF Setpoints
76
Float
R/W
Gen Pf Max Setpoint
Limit GG
PF
-1 - -0.5
PF Setpoints
76
Float
R/W
Gen PF Preposition 1 GG
PF
0.5 – -0.5
PF Setpoints
76
Float
R/W
Gen PF preposition 2 GG
PF
0.5 – -0.5