71
of 82
Operating Instructions Safety I/O Terminals SI4000 / SO4000
Dokument-Nr.: 5.08009.05
APPENDIX D - TECHNICAL DATA
In this appendix, you will find the technical data for Baumüller Nürnberg GmbH's Safety I/O ter-
minals.
D.1 Connection technology
Connection technology
Wiring Cage Clamp
®
spring-loaded system
Connection cross-section 0.08 mm² ... 2.5 mm², AWG 28-14, stranded wire, solid
wire
Field bus connection depending on fieldbus
Power contacts up to 3 blade/spring contacts
Current load 10 A
Nominal voltage depends on bus terminal type
D.2 Connection values
Product name SI4000
Number of inputs 4
Number of outputs 0
Status display 4 (one green LED per output)
Response time
(read input / write to I/O bus)
typical: 4 ms
maximum: see fault response time
Fault response time < watch dog time (adjustable from 5 ms to 100 ms)
Cable length between sensor and
terminal (unscreened line)
max. 100 m (at 0.75 mm² or 1 mm²)
Cable length between sensor and
terminal (screened line)
max. 100 m (at 0.75 mm² or 1 mm²)