EasyManua.ls Logo

Baxi iMPI/E V200 4-8 - Page 41

Baxi iMPI/E V200 4-8
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Status Appliance: AM012 parameter Appliance sub status: AM014 parameter
12 Load test CH max
30= normal operation. The compressor or the back-ups are running.
31= internal set point limited
If the heating set point on the heat pump differs from the system set point.
60= pump post-operation
Heat pump and back-up shut-down, system pump post-operation.
65= compressor bypass and back-ups running
66= the temperature exceeds the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
67= the outside temperature is lower than the compressor's maximum operat
ing temperature
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
69= defrosting running
The compressor is running.
70= defrosting conditions not provided
The compressor has stopped. The back-ups are operating.
71= defrosting running.
The compressor and the back-ups are running.
7 Reading out measured values
7700954 - v03 - 13082018 iMPI V200 41

Table of Contents

Related product manuals