Code Description Causes and corrective actions
Air temperature sensor T4 error
Communication fault: check the connection.
Damaged sensor: replace the sensor.
Air suction temperature sensor Th error
Communication fault: check the connection.
Damaged sensor: replace the sensor.
Air discharge temperature sensor Tp error
Communication fault: check the connection.
Damaged sensor: replace the sensor.
Tab.25 Px type error codes
Code Description Causes and corrective actions
High pressure error
Domestic hot water tank empty: fill the domestic hot
water tank with water.
Manual refrigerant valve closed: check the valve
openings.
Refrigeration tube pinched: check the refrigeration
tubes.
Excess refrigerant fluid: check the refrigerant fluid
content.
Non-condensables present: top up the refrigerant flu
id.
Water temperature sensor T5L poorly inserted in the
sensor tube: check the positioning of the sensor T5L.
Electrical overconsumption error on the compressor
Domestic hot water tank empty: fill the domestic hot
water tank with water.
Manual refrigerant valve closed: check the valve
openings.
Refrigeration tube pinched: check the refrigeration
tubes.
Excess refrigerant fluid: check the refrigerant fluid
content.
Refrigerant fluid fault: check the refrigerant fluid con
tent.
Non-condensables present: top up the refrigerant flu
id.
Water temperature sensor T5L poorly inserted in the
sensor tube: check the positioning of the sensor T5L.
Discharge temperature error: too high
Domestic hot water tank empty: fill the domestic hot
water tank with water.
Manual refrigerant valve closed: check the valve
openings.
Refrigeration tube pinched: check the refrigeration
tubes.
Excess refrigerant fluid: check the refrigerant fluid
content.
Refrigerant fluid fault: check the refrigerant fluid con
tent.
Non-condensables present: top up the refrigerant flu
id.
Water temperature sensor T5L poorly inserted in the
sensor tube: check the positioning of the sensor T5L.
Air temperature information outside the operating limits
Air temperature outside the operating limits of the heat
pump.
The electrical back-up ensures the production of do
mestic hot water.
Consumption error on the electrical back-up
The heat pump continues to operate but without electri
cal back-up
Consumption on the electrical back-up too low:
check the connection of the electrical back-up.
Consumption on the electrical back-up too high:
check the immersion heater.
If the set point temperature is greater than or equal
to 65 °C: set the thermostat to maximum.
11 Troubleshooting
54 7740327 - v03 - 03122019