RS232 - Interface
BC8050 und BC8150 69Version: 3.0.0
6.1.1.5.4 Function 6: writing an analog output
Function 6 can be used to access the output process image and the interface.
The first analog output is written with function 6. The analog outputs start at an offset of 0x0800. Here again
the offset always describes a word. This means offset 0x0803 refers to the fourth word in the output process
image.
Query
Byte Name Modbus RTU Modbus ASCII
Start - frame - - ":" 0x3A
Address 11 0x0B "0B" 0x30, 0x42
Function code 6 0x06 "06" 0x30, 0x36
Start address high 8 0x08 "08" 0x30, 0x36
Start address low 0 0x00 "00" 0x30, 0x30
Data high 63 0x3F "3F" 0x33, 0x46
Data low 255 0xFF "FF" 0x46, 0x46
Error check, LRC/
CRC
0xDA, 0xB0 "A9" 0x41, 0x39
End - frame t1-t2-t3 CRLF 0x0D, 0x0A
The Fieldbus Coupler Box responds with the same telegram and confirmation of the received data.
Response
Byte Name Modbus RTU Modbus ASCII
Start - frame - - ":" 0x3A
Address 11 0x0B "0B" 0x30, 0x42
Function code 6 0x06 "06" 0x30, 0x36
Start address high 8 0x08 "08" 0x30, 0x36
Start address low 0 0x00 "00" 0x30, 0x30
Data high 63 0x3F "3F" 0x33, 0x46
Data low 255 0xFF "FF" 0x46, 0x46
Error check, LRC/
CRC
0xDA, 0xB0 "A9" 0x41, 0x39
End - frame t1-t2-t3 CRLF 0x0D, 0x0A