BC8050 und BC8150 13Version: 3.0.0
2.4.2 Technical data - RS485
Fig.2: BC8050
System data RS485 (BC8050)
Protocols Address 1-39 serial ADS)*, KS8000 protocol (automatic recognition of
the protocol and the baud rate (9600, 19200, 38400 baud, fixed data
frame, 8 data bits, even parity, one stop bit)
Address 40-59 ModbusRTU (fixed baud rate 1200, 2400, 4800, 9600,
19200, 38400, DEFAULT 9600 baud, 8 bit data, optionally even, odd, no
default no parity)
Number of I/O modules 32 (99 with repeater)
Number of I/O points depending on controller
Data transfer medium shielded copper cable 2 x 0.25 mm², cable type A according to EN 50 170
Segment length up to 1200m
Data transfer rate 1200 - 38400baud
Topology RS485 line
Transmission time depending on protocol and baud rate
)* only via the configuration interfaces, not via RS485.