Commissioning
EL6631-0010 33Version: 3.4.0
Fig.10: Port diagnosis
4.1.4.3 Further diagnosis through the ADS interface
Additional diagnostic facilities are available through the ADS interface.
Read out the PROFINET name and the IP settings
An ADS READ block is to be used for this.
ADS WRITE Comment
AMSNETID AMS Net ID of the PROFINET device
PORT 0xFFFF (if a virtual PROFINET device is used, the port number is formed from
0x1000 + the device ID)
Index Group High Word - 0x0000, Low Word - 0xF804
Index Offset 0x0000
Length 257
Data byte offset Value Comment
0..3 reserved reserved
4..7 ARRAY4 of Byte IP Address
8..11 ARRAY4 of Byte Sub Net Mask
12..15 ARRAY4 of Byte Default Gateway
16...x STRING (max. length
240)
PROFINET Name

Table of Contents