10
The system is organised in menus that allow you to access varied features of the system: turn
luminaires on and off, perform Functional and Autonomy Tests, review information on mal-
functions etc.
To understand how to navigate among screens using the keys, see section "Keyboard and
Display Functions".
Most operations available can be applied to the entire system or to parts of it, as shown in the
following table:
There are 3 menus: LUMINAIRES, MAINTENANCE AND STATUS.
LUMINAIRES MENU
Use this menu to adjust the brightness of the luminaires:
MAINTENANCE MENU
MANUAL TEST
Functional and Autonomy Tests check the emergency luminaires. A Functional Test consists in
turning on a luminaire for about 30 seconds during which time the luminaire tube and battery
efficiency is checked; an Autonomy Test consists in turning on a luminaire over a longer time
at the end of which the battery efficiency is checked.
Normally, Functional and Autonomy Tests are run automatically at regular intervals according
to the schedule set by the user (see Scheduling Functional and Autonomy Tests"), but it is also
possible to perform a Functional Test or an Autonomy Test directly from the keyboard: Manual
Test. Manual Tests stop at the end of the set time or by sending a stop test command.
For: go to (menu):
all luminaires in the system ALL
a single luminaire (e.g. luminaire LOGICA SA
code F01234)
SA/PS F01234
all luminaires in Group yy GROUP 03
go to (menu):
for a maximum brightness level ON (MAX)
to turn them off TO TURN THEM OFF
for an intermediate brightness level (e.g.
level 5)
DIMMER STEP 05
MENU