GN-9289 User Manual
Page 47 of (70)
G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx
8.3.4.
Adapter Information Special Register (0x1100, 4352)
0x1100(4352)*
Read/
Write
1word
Master fault action option. (Disable : 0x0000, Enable :
0x0001)
This option can enable Master fault action option.
With master fault action, fault action can be activated with
master
communication failure. Default is disable.
Start address of input image word register. =0x0000
Start address of output image word register. =0x0800
Size of input image word register.
Size of output image word register.
Start address of input image bit. = 0x0000
Start address of output image bit. =0x1000
Size of output image bit.
Update time for cyclic data change (same as 0x1028)
0x110D(4365)
Read
1word
Current Dip Switch State and Field Power Status (MSB)
ex) DHCP/Booth enable, Dip SW(0x01), Field Power On =
0x110E(4366) Read
Expansion slot’s GT-number including GN
First 1word is adapter’s number, if GN-9289, then 0x9289
0x1113(4371) Read
Expansion slot Module Id.
First 1word is adapter’s module id.
0x1119(4377)
Read
1word
Hi byte is ModBus status, low byte is internal bus status.
Zero value means ‘no error’.
Internal bus status(G-Bus)
0x00 : No Error
0x01 : ERR_DIP_SWITCH
0x40 : ERR_CRC_LRC
0x80 : ERR_WATCHDOG
0x02 : CONNECT_FAULT
0x03 : CONFIG_FAULT
0x04 : NO_EXPANSION
0x05 : INVALID_ATTR_VALUE
0x06 : TOO_MUCH_DATA
0x07 : VENDOR_ERROR
0x08 : NOT_EXPECTED_SLOT
Adapter G-Series Revision.
After the system is reset, the new “Set Value” action is applied.
** If the slot location is changed, set default value automatically(all expansion slot are live).