GN-9289 User Manual
Page 53 of (70)
G-series GN-9289 Modbus TCP_UDP Rev. 1.01.docx
9.2.3. Instance Attributes
Instance
ID
Attribute
ID
Access
Rule
Name Data Type Value
1
1
Get
Vendor ID
UINT
741
DEC
(Crevis Co., Ltd)
2
Get
Device Type
UINT
0C
HEX
(Communications Adapter)
3
Get
Product Code
UINT
9000
HEX
(GN-9289)
4
Get
Revision
Major
Minor
Structure
of:
USINT
USINT
~ 9
~ 255
5
Get Status WORD Device status. Defined in standard.
6
Get Serial Number UDINT Unique Number
7
Get
Product Name
String
Length
ASCII
String
Short_Strin
g
USINT
STRING
4
DEC
9289,Modbus/TCP Adapter,GBUS
Vendor-specific
100
Get
Device Fault
Code
USINT
00
HEX
: Normal Operation
Bit 0: No expansion slot
Bit 1: Too many expansion slot
Bit 2: Overflow I/O size
Bit 3: I/O Configuration failure
Bit 4: EEPROM Checksum fault
Bit 6: Invalid Module ID
Bit 7: Firmware fault
104 Get
Firmware
Release Date
UDINT YYYYMMDD
HEX